Heat Pump Size Calculator

Estimate your home's heat loss on the coldest design day and the heat pump size worth looking at, using the official EPC default values and the design temperatures MCS installers must use.

Get an instant heat pump estimate for your home

See your cost after the £7,500 grant in seconds, plus free quotes from MCS-certified installers.

FreeNo ObligationCertified Installers

What Size Heat Pump Do I Need?

Describe your home and we'll estimate its heat loss on the coldest design day, using the same default values an EPC assessor uses and the design temperatures MCS installers must use.

Estimated peak heat loss

6.3kW

At -5.1C outside, 20C inside

Heat pump size to look at

7kW

Smallest common size at or above your heat loss

Heat loss per sq m

70W

Lower is easier for a heat pump

What air source heat pumps of 6kW to 8kW actually cost

£12,164

median installed price, before the grant

£4,664

after the £7,500 Boiler Upgrade Scheme grant

Median of 8,054 real installations in that size band in 2025/26. Source: DESNZ Boiler Upgrade Scheme statistics, August 2026 (installations with a paid voucher, England and Wales). The grant applies in England and Wales.

Where the heat goes

Walls2.9kW
Roof0.5kW
Floor0.7kW
Windows and doors1.3kW
Air leakage and ventilation0.9kW

What would shrink the heat pump

  • Fill the cavity walls: -1.5kW
  • Replace the windows with modern double glazing: -0.6kW
  • Top the loft up to 270mm: -0.3kW

An estimate, not a design. MCS installers must size a heat pump to cover at least 100% of a room-by-room heat load calculation to BS EN 12831-1:2017 (MCS standard MIS 3005-D), and that survey replaces this number. Our defaults: U-values from BRE's RdSAP 10 specification (June 2026), window area from RdSAP 2012 Table S4, design outdoor temperatures from MIS 3005-D Table 2 column B, a whole-house 20C indoors, a rectangular plan with 2.5m storeys, no thermal bridging allowance, and air leakage from SAP 10.2 with a minimum of 0.5 air changes an hour. Solid floors use the design temperature rather than the annual average MCS specifies, so that part errs high. Flats and homes with extensions or room-in-roof conversions will be less accurate.

The Short Answer

For a typical 1930s semi we'd look at a 5kW to 7kW unit, and in our view many homes need a smaller heat pump than they're quoted. In the Electrification of Heat trial the median installed unit was 2.07 times the home's heat loss.

On this calculator's model, a 90 sq m 1930s semi in the Midlands loses about 6.3kW on the coldest design day with unfilled cavity walls and 100mm of loft insulation. With the cavity filled and the loft at 270mm, that drops to about 4.5kW.

Use it as a sense check, not a design: an MCS installer has to do a room-by-room heat loss calculation before sizing anything. If their figure is very different, ask them to walk you through it.

How This Calculator Works

It does a simplified version of an installer's heat loss sum: for every wall, window, roof and floor, area times how easily heat passes through it (the U-value) times the difference between inside (20C) and outside on a design day, plus the heat carried away by air leaking out.

  • U-values are BRE's RdSAP 10 defaults, the values an EPC assessor uses when they can't see inside a wall.
  • Design outdoor temperatures are from the MCS standard MIS 3005-D, Table 2: from -1.5C in Plymouth to -5.9C in Glasgow.
  • Window area, air leakage and room heights use standard defaults (our assumptions where the EPC method doesn't give one).

It can't know your exact room sizes, extensions, a room in the roof or anything unusual about a wall. That's why it's a range-finder and the survey matters.

Typical Results by House Type

HomePeak heat lossPer sq mSize to look at
2015 detached new build, 120 sq m3.5kW29W3.5kW
1960s bungalow, filled cavity, 270mm loft, 75 sq m4.8kW64W5kW
1930s semi, cavity filled, 270mm loft, 90 sq m4.5kW50W5kW
Victorian mid-terrace, solid walls, 100mm loft, 85 sq m4.8kW56W5kW
The same terrace with one open chimney5.5kW64W6kW
1930s semi, unfilled cavity, 100mm loft, 90 sq m6.3kW70W7kW
1960s detached, unfilled cavity, 100mm loft, 120 sq m9.6kW80W10kW

All at the Midlands design temperature (-5.1C). Mid-terraces do well because they lose wall heat only through the front and back. On the semi, filling the cavity alone takes about 1.5kW off. If you have empty cavities, we'd fill them first: see our guide to insulating before a heat pump.

Why Bigger Isn't Safer

A report for the Committee on Fuel Poverty (DESNZ, May 2026) compared monitored systems. In the government's Electrification of Heat trial, heat pumps were a median 2.07 times the home's inferred peak heat loss, and 54% were more than twice it. In the HeatpumpMonitor.org dataset the median was 1.42 times.

The efficiency cost is real but, on this data, modest. In the HeatpumpMonitor data, systems oversized by less than 1.5 times averaged a seasonal performance of 3.99, and those oversized 2 to 2.5 times 3.38. The 2.5 to 3 times band scored 3.76, but on few systems. The report cites evidence that heat pumps sized at about 1.3 to 1.5 times the calculated peak heat loss do best. Oversizing certainly costs more to buy. You can't go below the heat loss, though: MCS requires the heat pump alone to cover 100% of the calculated heat loss at the design temperature.

Reading a Heat Pump's Size

The number in a model name is a label. Real output changes with the outdoor temperature and the flow temperature, so ask for the unit's output at your design temperature and design flow temperature from the manufacturer's data. That's the figure that has to beat your heat loss. The Boiler Upgrade Scheme has a ceiling of 45kWth for a single system (70kWth for a cascade), which only matters for very large homes.

What to Do With Your Number

  • Under about 6kW: one small unit, in our view.
  • About 6kW to 10kW: a mid-sized unit; get it confirmed by the room-by-room survey.
  • Insulation would cut it a lot: do the cheap jobs first, then get the survey.
  • Over about 10kW: large or leaky. Radiators and insulation matter more, and two surveys are worth it.
  • Any quote well above your number without a heat loss report explaining why: we'd question it. We'd accept up to about 1.5 times your heat loss (the best-performing range in the report above); between 1.5 and 2 times, ask the installer to justify it; past twice it, push back.

Every MCS quote should come with the room-by-room heat losses written down. Our guide to comparing quotes shows what else to expect, and the savings calculator what it would cost to run.